Q: Say panagsukimat ed ambetel tan mauran ya agew et mangipapanengneng na abeban tuloy ya IR. Antoy Guard terminal?
A: Say Guard (G) terminal et singa bypass valve pian naekal so onlelereg ya kuryente ed marutak tan ambetel ya paway na cable termination.
Say Problema ed Panag-awas ed Dalin:
• True Bulk Current (I_bulk): Onaagus manlapud konduktor, diad loob na insulasyon, ya anggad screen (dalin).
• Surface Leakage Current (I_leakage): Manlelesa ed basa/marutak ya paway na insulasyon.
• No anggapoy bantay: Sukaten nen Megger so dagup na kantidad. Say wet termination et manggawa ed dry cable ya singa sigpot ya antikey.
Panon ya Mankikimey so Guard (G) Terminal:
• Ibalkot a maong so andi-kakanaan ya copper wire ed akapaway ya insulasyon ed baetan na konduktor tan say screen.
• Ikonekta iyan alambre ed G terminal na megger.
• Say G et walad parehon potensyal na Positibo, balet say kaplesan ya dalan to et onlampas ed internal measurement shunt.
• Resulta: Anggapoy onlelereg ed tapew na tapew ya onloob ed sirkito na panagsukat. Napatnagan so tuan IR ed loob!