Saray relay ed lugar et kaukolan day power supply tan contact-wetting voltage — sarag kasi na test set ya iter itan?

 Sep 04, 2026

 Mangiter na mensahe .

 

Say protection relay et sakey a mabilay a kagawaan legan na panag-testing: kaukolan toy DC power parad saray electronics to, tan saray binary inputs tan outputs to et nepeg ya nabasaan na suston boltahe pian saray trip tan close commands et tua. Diad substation say boltahe et manlalapud baterya na istasyon (kaslakan et 110 V o 220 V DC). Diad test bench et anggapoy baterya na istasyon - kanian kaukolan ya salatan itan na relay test set.

6phase relay tester

I-relay so suplay na kuryente ed pasen -say integrated DC auxiliary output so mangiiter na pakayari ed relay ya susuboken ya direkta manlapud test set, kanian agla kaukolan so mangawit na nikaduman suplay na bangko odino baterya.

110 V / 220 V DC selection -say output et tuloytuloy ya na-adjust ed kaliberliber na standard station-levels na baterya, kanian say parehon set et mansusubok ed saray relay ya walay rating to parad 110 V DC tan 220 V DC (tan abeban-voltage logic a singa say 24/48 V).

Independent adjustment -say auxiliary channel et galvanically separated tan adjust independent ed saray test currents tan voltages, kanian sarag ton i-simulate so undervoltage na DC supply legan ya saray AC quantities et mansiansian agmanguman - sakey ya importantin tsek parad DC-supervision elements.

Realistic contact verification -lapud saray trip/close circuits et na-energize na real DC, say test set et nanengneng toy aktual ya contact performance (kaiba lay arcing tan bounce) imbes ya logic-level approximation.

Ipawit so Pantepet