Agmon balot usaren so melag ya test transformer parad andukey iran kable

 May 27, 2026

 Mangiter na mensahe .

 

T: Say 50 kV / 5 kVA test transformer ko - inkuan na boss ko ya "ikonekta mo labat ed 3 km ya kable." Walay naliliknak ya aliwan duga. Duga ak?

 

A: DUGA KA. AGMO IYA GAWAEN. Saya so #1 ya lingo na saray manbabaroy ya maneral ed saray transformer.

 

Problema #1: Baleg ya sobran karga

• 3 km 35 kV cable: C ≈ 0.5 μF. I_charge=50,000 × 314 × 0.5×10−6=7.85 A.

• Kaukolan ya pakayari: 50 kV × 7.85 A=393 kVA.

• Say transformer yo et 5 kVA. Mankekerew ka na 78× ya rated ya pakayari. Say winding et man-aso ed loob na pigaran segundo.

Problema #2: Waveform distortion

• Capacitive load → leading power factor → transformer core saturates.

• Say output waveform et magmaliw ya sankatageyan - say crest factor et ontagey manlapud 1.414 ya anggad 1.6-1.8.

• Say 50 kV RMS test et nayarin mamawala na 90 kV peak - ya agnakontrol ya overstressing.

Problema #3: Ag-onkualipika so regulasyon na boltahe

• No anggapoy karga, mangiletneg kay 50 kV.

• No mankonekta so kable, onleksab so boltahe ed 10-20 kV (say transformer et ag makapangiter na kuryente).

• Itagey so input → mas onsaturate so TX → onkupas so boltahe → onkapuy so fuse.

Kapigan so pangusar na test transformer parad saray kable?

Kable ed 35 kV

C

Kaplesan @ 50 kV

OK parad 5 kVA TX?

< 100 m

< 15 nF

< 0.24 A

❌ Siansia nin 2.4× so sobran karga

< 50 m

< 8 nF

< 0.12 A

❌ 1.2× overload

< 20 m

< 3 nF

< 0.05 A

✅ Diad loob na rating

Mairap ya totontonen: Mangusar labat na test transformer parad saray kable ya antikey nen ~25 metros. Parad antokaman ya mas andukey, mangusar na serye na resonant system.

 

Maples ya Giya ed Panpili

No suboken mo...

Manpili...

Rason

CT, PT, bushing, short bus bar

Suboktransformer

Simpli, mura, magenap so pakayari

Switchgear / 1-2 GIS bays

Suboktransformero melag ya SR

Parehon mantratrabaho

Distribution cable < 500 m

Melag ya SR (30-60 kV)

Kaukolan so Q-factor power saving

HV cable > 1 km

SR (100-300 kV)

Say sankaabigan labat ya opsyon

Generator stator

SR (20-30 kV high I)

Malinis ya waveform, atagey so kuryente

Transformer induced test

SR ya walay > 100 Hz

Kaukolan so frequency > rated

Rotina ed pabrika (parehon karga)

Subok so TX o say SR ya aka-fix

Standardized choice

Field test (nanduruman karga)

Modular SR

Say inka-flexible ed pangi-reconfigure

Ipawit so Pantepet
Ipawit so Pantepet