T: Say 50 kV / 5 kVA test transformer ko - inkuan na boss ko ya "ikonekta mo labat ed 3 km ya kable." Walay naliliknak ya aliwan duga. Duga ak?
A: DUGA KA. AGMO IYA GAWAEN. Saya so #1 ya lingo na saray manbabaroy ya maneral ed saray transformer.
Problema #1: Baleg ya sobran karga
• 3 km 35 kV cable: C ≈ 0.5 μF. I_charge=50,000 × 314 × 0.5×10−6=7.85 A.
• Kaukolan ya pakayari: 50 kV × 7.85 A=393 kVA.
• Say transformer yo et 5 kVA. Mankekerew ka na 78× ya rated ya pakayari. Say winding et man-aso ed loob na pigaran segundo.
Problema #2: Waveform distortion
• Capacitive load → leading power factor → transformer core saturates.
• Say output waveform et magmaliw ya sankatageyan - say crest factor et ontagey manlapud 1.414 ya anggad 1.6-1.8.
• Say 50 kV RMS test et nayarin mamawala na 90 kV peak - ya agnakontrol ya overstressing.
Problema #3: Ag-onkualipika so regulasyon na boltahe
• No anggapoy karga, mangiletneg kay 50 kV.
• No mankonekta so kable, onleksab so boltahe ed 10-20 kV (say transformer et ag makapangiter na kuryente).
• Itagey so input → mas onsaturate so TX → onkupas so boltahe → onkapuy so fuse.
Kapigan so pangusar na test transformer parad saray kable?
|
Kable ed 35 kV |
C |
Kaplesan @ 50 kV |
OK parad 5 kVA TX? |
|
< 100 m |
< 15 nF |
< 0.24 A |
❌ Siansia nin 2.4× so sobran karga |
|
< 50 m |
< 8 nF |
< 0.12 A |
❌ 1.2× overload |
|
< 20 m |
< 3 nF |
< 0.05 A |
✅ Diad loob na rating |
Mairap ya totontonen: Mangusar labat na test transformer parad saray kable ya antikey nen ~25 metros. Parad antokaman ya mas andukey, mangusar na serye na resonant system.
Maples ya Giya ed Panpili
|
No suboken mo... |
Manpili... |
Rason |
|
CT, PT, bushing, short bus bar |
Suboktransformer |
Simpli, mura, magenap so pakayari |
|
Switchgear / 1-2 GIS bays |
Suboktransformero melag ya SR |
Parehon mantratrabaho |
|
Distribution cable < 500 m |
Melag ya SR (30-60 kV) |
Kaukolan so Q-factor power saving |
|
HV cable > 1 km |
SR (100-300 kV) |
Say sankaabigan labat ya opsyon |
|
Generator stator |
SR (20-30 kV high I) |
Malinis ya waveform, atagey so kuryente |
|
Transformer induced test |
SR ya walay > 100 Hz |
Kaukolan so frequency > rated |
|
Rotina ed pabrika (parehon karga) |
Subok so TX o say SR ya aka-fix |
Standardized choice |
|
Field test (nanduruman karga) |
Modular SR |
Say inka-flexible ed pangi-reconfigure |