Antam so Ratio Error & Accuracy Classes na CT — 0.2, 0.5, 5P20

 Jun 03, 2026

 Mangiter na mensahe .

 

T: Panon kon naamtaan no dinan ya CT so parad metro ko tan no dinan so parad relay ko?

A: Saray CT et espisyal. Saray metro et kaukolan so inkasusto ed normal iran karga; kaukolan itan na saray relay legan na angkakabaleg iran depekto.

 

1. Klase na Pagsukat:

• 0.2s / 0.5s: Susto ya anggad 1% ya kuryente. Uusaren parad panagsingil na kita.

 

2. Klase na Proteksion:

• 5P20: 5% ya error ed 20 beses ya rated current. Uusaren parad saray relay.

Lingo: Agmon balot usaren so Meter CT (0.2) parad proteksion (man-saturate itan); ag ka balot mangusar na Protection CT (5P) parad panagsingil (aliwan susto).

 

Say CT ko et walay S1, S2, S3, S4, S5. Panon kon naromog so dugan ratio?

 

Saraya so "Tapped" CTs. Say panguman na koneksyon et manguman ed saray segundaryon liko tan ratio.

 

Saray Tip ed Pansubok:

• Amtaen so Kaslakan: Kaslakan et S1 so kaslakan.

• I-verify so Resistance: Say S1-S5 (sankatageyan ya turno) so walaan na sankatageyan ya resistensya.

• Ratio Math: No say S1-S2 et 100/5 (Ratio 20), say S1-S4 et nepeg ya 300/5 (Ratio 60).

Pro Tip: Agmon balot i-short-circuit so ag nausar ya gripo legan ya susuboken so sananey. Markaan iray ag nausar ya tap bilang N/C ed report mo.

Ipawit so Pantepet
Ipawit so Pantepet